Energy reporting and energy consumption monitoring in industry

Summary

Energy reporting tells you afterwards how much energy was used and where. Energy consumption monitoring shows the same continuously, so a deviation can be acted on in time. This article covers what a good energy report contains, how the figures are calculated correctly from meters and power readings, and how the reporting is automated.

At the turn of the month someone opens Excel, copies the meter readings, works out the differences and pastes the table into a report. The job repeats every month, and mistakes surface only when the figures fail to match the invoice. Energy reporting is easy to automate, because the measurements it needs are usually already in the automation system.

Energy reporting and energy consumption monitoring: what is the difference?

Energy reporting looks back: how much energy was used in a day, a week or a month, by site and by process stage. A report is a document that is filed, sent on and compared with the previous period.

Energy consumption monitoring is continuous: trends and views in which a deviation shows up the same day. Both need the same foundation, namely reliably stored measurements and one shared way of calculating consumption from them.

An energy management system often means a management system to ISO 50001: targets, responsibilities and continual improvement. Measured data and energy reports are its most important input, but not the whole system.

What does a good energy report contain?

  • Consumption by site and by period: electricity, heat, steam, fuel and water on rows of their own.
  • Specific consumption: consumption relative to output, for example kWh per tonne produced. Total consumption alone does not tell whether more energy was used or more was produced.
  • Peak power: the highest power in the period, if it matters for the contract or for sizing.
  • Comparison: the same period in the previous month or year.
  • Summary: sum, average, maximum and minimum over the period.

Where do the figures come from, and how are they calculated correctly?

Energy measurements reach the automation system in two forms, and each is handled differently:

Two ways of calculating consumption
MeasurementExampleConsumption in a period
Counter (cumulative)Energy meter reading, kWhThe change in the reading over the period. A counter reset must be detected, or the period gets a huge negative figure.
Instantaneous valuePower, kWPower multiplied by time: average power × the period's length in hours. Gaps in the data have to be taken into account.

A monthly report has two more traps. A month is not 30 days but 28 to 31, and on the days the clocks change a day lasts 23 or 25 hours. Monthly totals calculated with a fixed period length therefore do not match the billing periods.

How is energy reporting automated with DataPortia™?

DataPortia reads the energy measurements from the automation system's OPC UA server, stores them in a time-series database on the plant's own server and turns them into reports.

  • Counters: a measurement point is marked as a counter, so the report shows each period's change.
  • From power to energy: the calculation point IN1 * INTERVAL_H turns power (kW) into energy (kWh) for any report interval. For intervals longer than an hour the calculation is done per hour and summed, so gaps in the data do not distort the total.
  • Calendar periods: when the report interval is a day or a month, the rows follow the real calendar, also on the days the clocks change.
  • Specific consumption: the calculation point IN1 / IN2, when energy and output are measurements of the same kind: either both counters or both instantaneous values.
  • Scheduling and delivery: daily, weekly, monthly, quarterly and yearly reports as PDF, CSV or Excel files with your own template. A scheduled report runs at 00:15 once its period has closed, and it can be sent by e-mail if you choose.
  • Monitoring: the same measurement points and calculation points appear in trends and on dashboards.

A calculation point treats all its inputs the same way: either as counters or as instantaneous values. A counter and an instantaneous value are therefore not combined in one formula.

Reporting for district heating networks and building stock is covered on the building and district energy page, and finding savings with AI in Energy cost optimisation with AI.

Where to start?

Take your current monthly energy report and list its figures and meters. If the meters are visible on the automation system's OPC UA server, the same report can be built in DataPortia and run alongside the old one for a month. The trial lasts 30 days, includes every feature except the HA add-on and commits you to nothing.